Home/Writing the specification

For specifiers

Writing a spec under 09 67 23

There is no dedicated MasterFormat section for resinous static control flooring. The one static control number, 09 65 36, covers resilient tile and sheet goods, which is a different product[13]. A resinous ESD system is written into 09 67 23 Resinous Flooring, with its ESD performance stated in Part 2.

2.5 x 104 to 1.0 x 106ohmsANSI/ESD STM7.1 / ASTM D257 (as cited on manufacturer TDS)
under 1.0 x 109ohmsANSI/ESD STM97.1
under 80percent RHASTM F2170
What an ESD floor is made of, top to bottomESD topcoat5 to 7 mils applied, 6 typicalConductive basecoatcarries the charge across the floorGrounding networktied into the building groundPrimerbonds the system to the slabPrepared concreteopened mechanically, under 80% internal RHTO BUILDING GROUND
The charge runs down through the system to the building ground. That path is what gets measured point to ground.

Writing the specification

01

Name the band, not the adjective

'Static control epoxy' is not a specification. The band, the test method and the standard your program runs to are what make it enforceable at closeout.

02

Specify the system, not the topcoat

Manufacturer warranties are generally tied to installing the full specified system, primer, basecoat and topcoat, rather than a substituted product in the middle. Say so in Part 2 or a substitution will arrive at bid.

03

Put the moisture test in the spec

ASTM F2170 slab relative humidity readings, taken in situ at the locations and density you want, before installation[12]. If it is not specified it becomes a change order the week work starts.

04

Say what gets handed over

Product data, the system cross section, the surface prep profile, moisture readings and a grounding drawing. Naming the closeout package in the spec is what makes it exist.

05

Reference the program, not just the product

Cite ANSI/ESD S20.20[1] or IEC 61340-5-1[6] explicitly. It tells every bidder which world they are in and which test methods apply.

06

Write the reverification in

ESD TR53 covers compliance verification for items already in service[17]. A spec that ends at day one hands the facility an unowned obligation.

The performance lines to write

Copy these into Part 2. A specification that says "ESD epoxy" and stops cannot be enforced against anybody, including us.

LineWhat to specifyCite
Resistance band2.5 x 104 to 1.0 x 106 ohms (conductive) or 1.0 x 106 to 1.0 x 109 ohms (dissipative)ANSI/ESD STM7.1
System resistanceUnder 1.0 x 109 ohms, person plus footwear plus floorANSI/ESD STM97.1
Walking voltageUnder 100 voltsANSI/ESD STM97.2
Slab moistureUnder 80 percent internal RHASTM F2170
Vapour emission8 to 10 lbs / 1,000 sq ft / 24 hrASTM F1869
Program standardANSI/ESD S20.20 or IEC 61340-5-1Name the one you run to
Section09 67 23 Resinous Flooring, Part 2 performanceCSI MasterFormat

Questions

Which CSI section does resinous ESD flooring go under?

09 67 23 Resinous Flooring, with the ESD performance written into Part 2. 09 65 36 Static-Control Resilient Flooring is a different product category, resilient tile and sheet, not a resinous coating[13].

What is the minimum enforceable ESD line in a spec?

A resistance band, a test method, and the program standard. Those three make it possible to accept or reject the finished floor on evidence rather than opinion.

Should the spec name a manufacturer?

That is your call as the specifier. What matters more is that the performance lines are written so any compliant system can be measured against them. Send us the draft section and we will tell you what a bidder will read into it.

Sources

Publishers cited on this page, and how many times each one is citedesda.org2buildsite.com1store.astm.org1webstore.iec.ch1
5 citations on this page, across 4 publishers. Every figure above is one of them.
  1. ANSI/ESD S20.20-2021, the ESD control program standard for electronics handling

    ESD control program requirements (administrative and technical) for any organization that handles ESD-sensitive electrical or electronic parts.

    www.esda.org
  2. IEC 61340-5-1:2024 Edition 3, the international ESD control program standard

    International equivalent of ANSI/ESD S20.20: general requirements for an ESD control program protecting electronic devices.

    webstore.iec.ch
  3. ASTM F2170-19a, in situ concrete slab relative humidity test before coating

    Determining relative humidity inside a concrete slab using in-situ probes; the moisture test a slab has to pass before an epoxy topcoat goes down.

    store.astm.org
  4. CSI MasterFormat 09 67 23 Resinous Flooring, the section an ESD spec is written under

    The base specification section a resinous ESD/conductive epoxy system is written under. MasterFormat has NO dedicated static-control subsection under 09 67 23. The only dedicated.

    www.buildsite.com
  5. ESD TR53, compliance verification testing for ESD control items already in service

    Technical report for compliance verification testing of ESD control items already in service; the document a facility's periodic floor-resistance recheck follows.

    www.esda.org

Every number on this page came from one of those documents. Send us the room and we will tell you which of them your floor has to answer to.