Home/Standards/CSI 09 67 23

Standard

CSI 09 67 23

Resinous Flooring. The MasterFormat section a resinous ESD system is specified under, because there is no dedicated static control resinous number.

5 to 7 (6 typical)milsmanufacturer TDS, Kretus SELECT ESD Epoxy Conductive/Dissipative, Rev. 5/28/24
under 80percent RHASTM F2170
8 to 10lbs per 1,000 sq ft per 24 hoursASTM F1869

What it means for your floor

ESD topcoat5 to 7 mils applied, 6 typicalConductive basecoatcarries the charge across the floorGrounding networktied into the building groundPrimerbonds the system to the slabPrepared concreteopened mechanically, under 80% internal RH

To building ground

The charge runs down through the system to the building ground. That path is what gets measured point to ground.
01

There is no dedicated resinous ESD section

MasterFormat has no static control subsection under 09 67 23. The one dedicated static control flooring number, 09 65 36, governs resilient tile and sheet goods, which is a different product category from a resinous coating.

02

So it goes in Part 2 as performance

A resinous system's ESD performance is written into 09 67 23 Part 2 as a performance requirement: the resistance band, the test method, and what has to be handed over. That is the correct home for it, not a borrowed section number.

03

What to put in the performance line

Name the band, name the test method, and name the standard your program runs to. A spec that says 'ESD epoxy' and stops is a spec that cannot be enforced.

CSI 09 67 23what it asks of a floor