General requirements for an ESD control program protecting electronic devices. Edition 3.0 published in 2024.

lowest annual RH the facility experiencescondition, not a fixed percentageIEC 61340-5-1:2024
3.5 x 107ohmsIEC/EN 61340-5-1

What it means for your floor

Where conductive and static dissipative sit on the resistance scale 10³10⁴10⁵10⁶10⁷10⁸10⁹10¹⁰10¹¹10¹²10¹³ CONDUCTIVE STATIC DISSIPATIVE INSULATIVE 2.5 x 10⁴ to 1.0 x 10⁶ ohms. Fastest bleed. Specified where a spark is the hazard. Anything above 10⁹ is an insulator and holds a charge instead of moving it. ANSI/ESD STM7.1 · bands published by the ESD Association
The two static control bands, drawn where they sit on the scale. Everything to the right of 10⁹ ohms is an insulator.
01

Edition 3.0 changed the humidity rule

The 2024 edition lets a facility qualify its ESD control items, flooring included, at the lowest relative humidity that facility actually experiences across the year, rather than against a fixed arbitrary low humidity benchmark. For a Texas plant with a dry winter and a wet summer that is a meaningful difference in what the certificate describes.

02

It also defined two terms formally

Edition 3 added formal definitions of insulator and isolated conductor. Those definitions matter for what has to be controlled in a room, not only for the floor.

03

The legacy series path

EN and IEC 61340-5-1 still carry the 3.5 x 107 ohm ceiling for a person, footwear and floor measured in series, the approach S20.20 used before 2014. A spec quoting that number is on this path, not out of date.