The Health Care Facilities Code. It used to require conductive flooring in operating rooms. That requirement came out in 2015.

2.5 x 104 to 1.0 x 106ohmsNFPA 99 (historical, pre-2015 editions)

What it means for your floor

Where conductive and static dissipative sit on the resistance scale 10³10⁴10⁵10⁶10⁷10⁸10⁹10¹⁰10¹¹10¹²10¹³ CONDUCTIVE STATIC DISSIPATIVE INSULATIVE 2.5 x 10⁴ to 1.0 x 10⁶ ohms. Fastest bleed. Specified where a spark is the hazard. Anything above 10⁹ is an insulator and holds a charge instead of moving it. ANSI/ESD STM7.1 · bands published by the ESD Association
The two static control bands, drawn where they sit on the scale. Everything to the right of 10⁹ ohms is an insulator.
01

What changed and when

NFPA 99 historically required conductive flooring in the 2.5 x 104 to 1.0 x 106 ohm range in operating rooms using flammable anesthetics. That requirement was removed in the 2015 edition and is still absent from the current 2024 edition.

02

Why it was removed

Flammable inhaled anesthetics are essentially gone from US surgical practice, so the ignition risk the requirement existed to control went with them.

03

What this means if somebody cites it to you

NFPA 99 still governs health care facility construction broadly. It simply no longer carries this resistance range. If a specification cites NFPA 99 as the reason for a conductive floor, it is worth going back to the source before you buy to that band.